Control Devices: respect "resolution" when reading "inputValue" #128

Merged
merged 1 commit into from
May 3, 2024

Conversation

jktjkt
Copy link
Contributor

@jktjkt jktjkt commented Aug 20, 2023

The standard (62386-103:2014, chapter 9.7) states that the "resolution" of an instance is not always 8-bits. If it's any longer, a proper read involves a transaction and a sequence of commands. If the number is not divisible by 8, extra trailing bits have to be truncated.

Tested on Lunatone DALI-2 MC (86459532-2) and Lunatone CS-2 (86458670). The push button coupler is a part-301 device where the standard says that the on-the-wire values are either 0x00 or 0xff, but the actual resolution (and therefore the correct numeric value) is either 0 or 1. The other device, a combined movement sensor with a light meter, supports 11 bits of resolution for the lux meter and therefore it requires a "QUERY INPUT VALUE" followed by a "QUERY INPUT VALUE LATCH" and dropping the extra 5 bits.

@sde1000
Copy link
Owner

sde1000 commented Aug 22, 2023

Looks good, thank you.

Ideally there would be a test for this new sequence in test_device_sequences.py

@jktjkt jktjkt force-pushed the multibyte-inputvalue branch 2 times, most recently from 2931995 to 8fbf79f Compare April 26, 2024 00:34
The standard (62386-103:2014, chapter 9.7) states that the "resolution"
of an instance is not always 8-bits. If it's any longer, a proper read
involves a transaction and a sequence of commands. If the number is not
divisible by 8, extra trailing bits have to be truncated.

Tested on Lunatone DALI-2 MC (86459532-2) and Lunatone CS-2 (86458670).
The push button coupler is a part-301 device where the standard says
that the on-the-wire values are either 0x00 or 0xff, but the actual
resolution (and therefore the correct numeric value) is either 0 or 1.
The other device, a combined movement sensor with a light meter,
supports 11 bits of resolution for the lux meter and therefore it
requires a "QUERY INPUT VALUE" followed by a "QUERY INPUT VALUE LATCH"
and dropping the extra 5 bits.

The test case comes from Lunatone's doc "DALI-2 Devices for
Integration, DALI-2 Instances, DALI-2 Instance Mode".
@jktjkt
Copy link
Contributor Author

jktjkt commented Apr 26, 2024

Ideally there would be a test for this new sequence in test_device_sequences.py

Done -- and sorry for a "slight" delay :).

@sde1000 sde1000 merged commit 73ba41f into sde1000:master May 3, 2024
5 checks passed
@jktjkt jktjkt deleted the multibyte-inputvalue branch July 26, 2024 15:30