Expand Up @@ -122,3 +122,29 @@ Correct WC value depends on how many and which devices are configured.
Domain1: State 2. is good state
AL states: OP. means all slave devices are operational
# Advanced devices
Some devices like many servo drives will not start up unless they are correctly configured, which involves Service Data Objects
OpenPLC and ethercat_src provide no means to configure SDOs, but IgH EtherCAT master does
For example, running the following script before starting OpenPLC prepares EL7047 stepper driver in pos 4 for OP mode, it will not enter OP mode without this configuration
```bash
ethercat states preop
sleep 3
ethercat download -p 4 -t uint16 0x10f3 5 0x0000
ethercat download -p 4 -t uint32 0xf081 1 0x00100000
ethercat download -p 4 -t uint8 0x1c12 0 0x00
ethercat download -p 4 -t uint8 0x1c13 0 0x00
ethercat download -p 4 -t uint16 0x1c12 1 0x1600
ethercat download -p 4 -t uint16 0x1c12 2 0x1602
ethercat download -p 4 -t uint16 0x1c12 3 0x1604
ethercat download -p 4 -t uint16 0x1c13 1 0x1a00
ethercat download -p 4 -t uint16 0x1c13 1 0x1a03
ethercat download -p 4 -t uint8 0x1c12 0 0x03
ethercat download -p 4 -t uint8 0x1c13 0 0x02
```
The specific list of parameters and in which order they have to be written is device specific, one way to determine correct configuration is to set the device up in TwinCAT or other commercial EtherCAT capable PLC software and copy the configuration from there. For example [startup tab in TwinCAT](https://infosys.beckhoff.com/english.php?content=../content/1033/tc3_io_intro/1345265931.html&id=)