You signed in with another tab or window. Reload to refresh your session.You signed out in another tab or window. Reload to refresh your session.You switched accounts on another tab or window. Reload to refresh your session.Dismiss alert
check that when a DA with FC=SE, SG, SP has valImport=true, the LN0.NamPlt contains paramRev
See IEC 61850-7-2 ed2.1 annex C (normative) : Tracking of configuration revisions
See IEC 61850-6 ed2.1: "Where a system configurator also changes configuration values and parameter values for an IED, it has also to increment the appropriate paramRev and valRev attributes in the LN0 NamPlt as well as other LNs having appropriate NamPlt attributes. "
The text was updated successfully, but these errors were encountered:
I'm submitting a ...
[ ] bug report [X] New constraint to add
Describe your new constraint here
check that when a DA with FC=SE, SG, SP has valImport=true, the LN0.NamPlt contains paramRev
The text was updated successfully, but these errors were encountered: