The APC UPS plugin monitors uninterruptible power supplies from Cacti. It reads
UPS status from an apcupsd daemon, from a Network UPS Tools (NUT) upsd
server, or from a UPS that has an SNMP agent, stores the readings in the Cacti
database, and shows them on a fleet dashboard and on a dashboard for each UPS.
It is for administrators who need to track data center or office UPS units that
do not offer SNMP themselves but are reachable through apcupsd or NUT.
This page follows the plugin's develop branch, which is unreleased and can
change. That branch declares plugin version 1.4.0 and Cacti compatibility
1.2.29 in its INFO file. Check the release you install for differences.
- Plugin version 1.4.0 and Cacti 1.2.29 or later, as declared in
INFO. - The plugin does not require other plugins.
- For a UPS of type APC UPSD Based, the
apcupsddaemon on the UPS host with its network information server enabled (NETSERVER on, TCP port 3551 unlessNISPORTsays otherwise). The Cacti poller must be able to open a TCP connection to it. - For a UPS of type NUT Based, a NUT
upsdserver that the poller can reach, by default on TCP port 3493. TheopensslPHP extension is needed for the Use TLS (STARTTLS) option. - For a UPS of type SNMP Based, a Cacti device with working SNMP settings.
apcupsd,apcaccess, and the NUT client tools do not have to be installed on the Cacti poller. The plugin speaks both network protocols itself.- The Cacti poller. The plugin starts its collector at the end of every polling
cycle, using the PHP binary configured in Cacti (
path_php_binary). - The
INFOfile declares support for remote data collectors (remote_collect:1). Each UPS has a Poller ID, and the plugin replicates its UPS tables to remote pollers.
Follow Plugin Management to install and enable the plugin. The
directory must be named apcupsd. Plugin-specific steps:
- Import the device package from the plugin's
templatesdirectory,UPS_APC_UPSD_Device_12x.xml.gz, with Console > Import/Export > Import Templates. It supplies the device template that the plugin uses to create a Cacti device for each UPS. Until it is imported, the poller writes the log lineUPSD Device Package Not Imported. Device automation will not happen until it is imported!and does not create devices. - Enable the network information server on each
apcupsdhost. Inapcupsd.conf,NISIPis the address the daemon listens on, not a list of allowed clients. The default0.0.0.0listens on every interface. Allow the poller in through the host firewall on the server port. The README notes that the network information server has no authentication and is read-only, so expose it only to networks you trust. - For NUT,
upsdlistens on localhost by default. To let the poller reach it, add aLISTENline toupsd.conf(for exampleLISTEN 0.0.0.0 3493), restartupsd, and allow the poller through the firewall.
The dashboards read each reading's minimum, average, and maximum from the RRD files of the UPS's Cacti device, so the device needs its graphs. If a device has none, for example because the package was imported afterward, select the UPS on the UPSes page and choose Run Graph Automation from the action drop-down. This action is offered only to users who have the permission equivalent to Cacti's Apply Automation Rules device action.
When the version in INFO differs from the stored version, the plugin
reconciles its tables the next time Plugin Management or the UPSes page
is opened.
| Realm | Pages |
|---|---|
| Manage UPS's | upses.php: the UPS list, UPS editor, UPS dashboards, and fleet dashboard |
The plugin adds this realm to Cacti's System Administration role when the role helper exists.
The plugin adds no tab to Console > Configuration > Settings. All configuration is per UPS, on the UPS editor page. Open Console > Management > UPSes, then add a UPS or edit an existing one.
| Field | Default | Purpose |
|---|---|---|
| UPS Name | New UPS | The name of the UPS. For apcupsd and NUT UPSes, a Cacti device with this name is created automatically. For SNMP UPSes, create the Cacti device first. |
| UPS Description | A longer description. | |
| UPS Type | APC UPSD Based, SNMP Based, or NUT Based. | |
| Poller ID | 1 | The poller that monitors this UPS. |
| Site Name | The site the UPS belongs to. | |
| Location | Free-form physical location, such as a room or rack. | |
| Cacti Device | Autocreate on First Poll | For SNMP UPSes, the Cacti device that supplies the SNMP credentials. Otherwise select None and the plugin creates the device. |
| Enabled | on | Starts polling the UPS immediately. |
The APC UPSD Information section applies to apcupsd and NUT UPSes:
| Field | Default | Purpose |
|---|---|---|
| Hostname | The host running apcupsd or the NUT server (upsd). |
|
| TCP Port | The TCP port. apcupsd defaults to 3551 and NUT to 3493. |
|
| Timeout (seconds) | 5 | How long the poller waits for the server, from 1 to 120 seconds. SNMP UPSes use the SNMP timeout instead. |
The NUT Options section applies to NUT UPSes:
| Field | Default | Purpose |
|---|---|---|
| NUT UPS Name | The UPS name on the NUT server, as listed by upsc -l. One server can serve several UPSes; add one UPS per name. |
|
| NUT Username | Optional upsd.users account. Leave blank for anonymous read-only access. |
|
| NUT Password | The password for the NUT user. | |
| Use TLS (STARTTLS) | off | Encrypts the connection before credentials are sent. The server certificate and host name are verified. |
| CA / Certificate File | Optional full path on the poller to a PEM file with the CA certificate, or the self-signed server certificate, to verify the server against. The host name must match the certificate. | |
| Allow Self-Signed Certificate | off | Accepts any certificate without checking it. The setting's description advises preferring the certificate file. |
The SNMP Options section applies to SNMP UPSes and takes the hostname of the SNMP agent.
Console > Management > UPSes opens the UPS list, with the tabs UPSes and
Fleet Dashboard. The list shows, per UPS, the name, status, collector, UPS
status, model, line voltage, load percent, estimated power, time left,
Hostname:Port, enabled state, and last update time. Select UPSes and use the
action drop-down:
| Action | Effect |
|---|---|
| Delete | Deletes the selected UPSes. |
| Enable | Starts polling the selected UPSes. |
| Disable | Stops polling the selected UPSes. |
| Duplicate | Copies the selected UPSes under a new name. |
| Reset Detection | Clears the stored list of SNMP readings that the poller skipped for the UPS. |
| Run Graph Automation | Runs graph automation for the linked Cacti device. |
The Fleet Dashboard shows these cards: Fleet Overview, Status Distribution, Fleet Readings, Fleet Power, Fleet Gauges, and UPSes. A Timespan drop-down sets the period for the readings, Add a card adds a card you removed, and Refresh sets an automatic refresh interval.
The following screenshot shows the Fleet Dashboard. The example uses synthetic data from three test UPSes.
Selecting a UPS opens its UPS Dashboard with the cards UPS Information, one gauge card per available reading, Estimated Power, Input and Load, Battery and Runtime, and Events and Transfers.
- Open Console > Management > UPSes and add a UPS.
- Enter a UPS Name and choose the UPS Type.
- Enter the Hostname and TCP Port. For NUT, also enter the NUT UPS Name and, if needed, the credentials and TLS options.
- Leave Enabled checked and save.
- After the next polling cycle, the plugin creates the Cacti device for an
apcupsdor NUT UPS if the device package is imported.
For a UPS with SNMP, select the Cacti Device that holds its SNMP credentials instead.
The plugin registers the poller_bottom hook. At the end of each Cacti polling
cycle it starts poller_apcupsd.php in the background. The poller handles the
enabled UPSes of each type that belong to its own poller ID, in this order:
apcupsd, SNMP, NUT. It stores the readings in the plugin's tables
apcupsd_ups and apcupsd_ups_stats and writes a summary line tagged
APCUPSD STATS to the Cacti log.
- APC UPSD Based: the poller asks the daemon for its status over the
apcupsdnetwork protocol. - NUT Based: the poller talks to
upsdwith a PHP implementation of the NUT protocol. NUT power flags are translated to theapcupsdvocabulary (OLbecomesONLINE,OBbecomesONBATT,LBbecomesLOWBATT,RBbecomesREPLACEBATT,OVERbecomesOVERLOAD), so the dashboards treat both types the same way. - SNMP Based: the poller reads the UPS through the linked Cacti device's SNMP settings.
The estimated watts shown on the dashboards are computed from the nominal power
rating and the load. The README states that measured real power from NUT
(ups.realpower) is not stored yet.
The poller script is normally started by Cacti. It can be run by hand from any directory as the user Cacti runs as:
php plugins/apcupsd/poller_apcupsd.php [--force] [--debug]--debug prints more output. --version prints the version.
- No Cacti device is created: import the device package. Without it the
poller logs
UPSD Device Package Not Imported. - Log message
apcupsd query for UPS ... failed: the poller could not read status from theapcupsdserver. Check the hostname, port, and firewall, and thatNETSERVERis on. ANUT query for UPS ... failedmessage means the same for a NUT server. - Cannot connect from a remote poller:
NISIPset to127.0.0.1makesapcupsdaccept only local connections. - Dashboards show no min, average, or max values: the UPS's Cacti device has no graphs. Run Run Graph Automation from the UPS list.
- UPS not polled: check that Enabled is on and that the UPS's Poller ID matches the poller that runs the collector.